29 topics · 2026 NEC

Calculations for the Minnesota electrician exam

DLI's examination guide teaches the calculation types the exam uses: Ohm's law, voltage drop, transformers, conduit and box fill, ampacity and motors. Every topic here has unlimited problems with new numbers, a worked solution and the 2026 NEC section to open.

Live practice

Mixed practice: every topic

Each problem uses new numbers, so you practice the method rather than memorizing an answer.

Dwelling load calculations

Services and feeders for houses and apartments under Article 120.

Dwelling optional load calculation

The optional method adds every general load at nameplate (2 VA/ft² lighting, 1,500 VA per small-appliance and laundry circuit, range, dryer, water heater and other appliances), takes the first 8 kVA at 100% and the rest at 40%, then adds the heat or AC load from 120.82(C) and any EV charger at 100%.

JourneyworkerMaster120.82(A)

Dwelling standard load calculation

The standard method adds the dwelling loads one group at a time, each with its own demand factor: general lighting at 2 VA/ft² plus 1,500 VA per small-appliance and laundry circuit through Table 120.45, 75% of four or more fastened appliances, the dryer, the range from Table 120.55 and the larger of heat or AC.

JourneyworkerMaster120.41

Fastened appliance demand load

In a dwelling standard calculation, add the nameplate ratings of the fastened-in-place appliances such as the water heater, dishwasher, disposal, trash compactor and built-in microwave.

JourneyworkerMaster120.53

Feeder and service neutral load

The neutral carries only line-to-neutral load, so leave out 240 V loads such as the water heater, heat and AC.

JourneyworkerMaster120.61(A)

Multifamily optional load calculation

For three or more dwelling units that each have electric cooking and electric heat or AC, add each unit's connected load (2 VA/ft², 1,500 VA per small-appliance and laundry circuit, appliance nameplates and the larger of heat or AC), multiply by the number of units, then by the Table 120.84 demand factor for that many units.

Master120.84(A)

Commercial load calculations

Lighting, receptacles and kitchen equipment in other occupancies.

Conductors and overcurrent

Ampacity, derating, voltage drop, continuous loads and breaker sizes.

Motors

Full-load current, conductors, overloads, branch-circuit and feeder protection.

Boxes and raceways

Box fill, conduit fill and pull box sizing.

Grounding and bonding

Equipment grounding and grounding electrode conductor sizes.

Transformers

Primary and secondary current and overcurrent protection.

Electrical theory

Ohm’s law, power, circuits, three-phase and power factor.